Model NO.: TA-1633
Application Range: Substation, Building
Shell Material: Steel Plate
Shell Protection Grade: IP56
Brand: Tianan
Rated Insulation Voltage: 660( 1000)V
Altitude: up to 3, 000m Above Sea Level
Environment: Outdoor
Special Conditions: Depends on The Customer
Rated Voltage of Main Circuit( V): AC 380( 400, 660)
Busbar: 3-Phase and 4-Wire
Test Equipment: IEC Standard
Typical Products: Kyn28A-12(Z)
Frequency: 50( 60)
Warranty: 10 Years
Trademark: Tianan Electric
Specification: IEC60076-1, IEC60076-2, IEC60076-5
Origin: Xiangshan Zhejiang P. R China
HS Code: 8537209000
KYN28A-12(Z) Metalclad Modular Switchgear Compact Switchgear
NINGBO TIANAN (GROUP) CO., LTD.
General
>>Ratings: system voltage 3.6kV, 7.2KV, 12KV, 24KV,rated current up to 4000A,Â
          AC three phase 50/60HZ.
>>Application: mainly applicable in the power plant, substation, mineral enterprise to receive andÂ
             Distribute power with the functions of controlling, protecting and monitoring. It also can be Â
             used in places where the frequently operations are in need.
>>Standard:Â IEC62271-200.
Working Conditions
1. Ambient air temperature: -15°C~+40°C.
2. Altitude: ≤1000m.
3. Relative humidity : Daily average≤95%, daily averange of vapour pressure≤2.2kpa.
4. Earthquake intensity: ≤magnitude 8.
5. Applicable in the places without corrosive and flammable gas and water vapor.
6. Used in place without frequently intense vibrant.
  Note: Customized products are available.
Specifications
Item |
Unit | Data | |||
Rated voltage | kv | 3.6, 7.2, 12,24KV | |||
Rated frequency | hz | 50 | |||
Rated current of circuit breaker | A | 630, 1250, 1600, 2000, 2500, 3150, 4000 | |||
Rated current of switchgear | A | 630, 1250, 1600, 2000, 2500, 3150, 4000 | |||
Rated short-time withstands current(4s) | ka | 16, 20, 25, 31.5, 40, 50 | |||
Rated peak withstands current (peak value) | ka | 40, 50, 63, 80, 100, 25 | |||
Rated short-circuit breaking current | ka | 16, 20, 25, 31.5, 40, 50 | |||
rated short-circuit making current (peak value) | ka | 40, 50, 63, 80, 100, 25 | |||
Rated insulation level | 1min power frequency withstands voltage | pole to pole, pole to ground | kv | 24, 32, 42 | |
fracture to fracture | kv | 24, 32, 48 | |||
lightning withstands voltage(peak) | pole to pole, pole to ground | kv | 40, 60, 75 | ||
fracture to fracture | kv | 46, 70, 85 | |||
Protection degree | Enclosure is IP4X. IP2X when CPT and CB door are open | ||||
Note: 1. The short-circuit capacity of current transformer is considered separately.                                                                                                          2. Details of the parameters of ZN 63A-12 as per reference company' s sample. | |||||
Â
 Â
Industrial Aluminum Alloy Die Casting
Industrial Aluminum Alloy Die Casting,Precision Magnesium Parts,Precision Pressure Cast Mold,Custom Auto Casting Parts
Dongguan Metalwork Technology Co., LTD. , https://www.dgdiecastpro.com